본문 바로가기

Vortec

Vortec

Vortec

In 1961, Vortec became the first company to develop technology for converting the vortex tube phenomenon into practical, effective industrial cooling solutions. Since then, Vortec has continued to refine and expand vortex tube applications, as well as develop air amplification products for more efficient use of compressed air in cleaning and conveying applications. In 1990, Vortec was purchased by Illinois Tool Works, a Fortune 200 company; and is now part of the ITW Air Management business unit, which, in addition to Vortec products, offers the Paxton Product line of products for drying and blow off.
Products
PROTEX VORTEX A/C
  • OVERVIEW
  • FEATURES
  • SPECS

PRODUCT OVERVIEW

ProtEX Vortex A/C Coolers are designed specifically for purged * Electrical enclosures in ATEX Zones 1 and 21, UL Class I, Div. 1 (Groups A,B,C and D), Class II, Div. 1 (Groups F and G), Class III and Temperature Class T3 areas. The ProtEX Vortex A/C incorporates the most up-to-date features into Vortec’s line of highly reliable, cost-effective enclosure coolers.

  • Sleek, modern design
  • Noise reduction of 78%, when compared to other vortex enclosure coolers
  • Energy use reduction through its integral mechanical thermostat
  • Filter contains pressure dop indicator notifying you of needed filter changes
  • Quick and easy installation in about 5 minutes
  • Flexible installation: top, side or front (door) mount
  • Incorporates check valve to prevent loss of enclosure pressure when cooling is not required
  • ATEX Certification Ex II 2 GD
  • UL Classified Class I Div. 1, Class II Div. 1, Class III
  • Ex h llC T200C Gb
  • Ex h lllC T200°C Db
  • Ta+10 to +80C
  • T3 Temperature Class rating

The ProtEX Vortex A/C is available in 4 different cooling capacities; 900,1500,2500 and 5,000 BTU/hr. All of Vortec’s Enclosure Coolers keep Electrical and Electronic Enclosures cool, clean and protected and are a low cost alternative to expensive, high maintenance air conditioners; and avoid contamination with dirty, humid air caused by fans. Today’s small, compact multi-function electronic controls, variable speed drives, servos and programmable logic controllers are extremely sensitive to heat and contamination. Smaller cabinet sizes make temperature control difficult and prone to premature failures. Excessive heat will cause digital displays to misread, controls to drift, and breakers to trip below rated loads. The result is productivity lost due to machine or line shutdowns.

ProtEX Vortex A/Cs maintain a slight pressurization on the cabinet to keep electrical and electronic components clean and dry; and most are thermostatically controlled to maintain enclosure temperatures within a specified temperature range.

* Purge system not included with purchase

BENEFITS

  • Easy to install, takes about 5 minutes
  • No wiring required to install
  • ATEX Certified for Zones 1 and 21
  • UL Classified for Class I Div. 1 (Groups A,B,C and D), Class II, Div. 1 (Groups F and G) and Class III
  • Thermostatically controlled to maintain enclosure temperatures within ideal range
  • Filter contains pressure dop indicator notifying you of needed filter changes
  • Highly reliable, with full 3 year warranty
  • No ambient, dirty or humid air enters the cabinet
  • Can be used on all cabinets, even in tight spaces
  • Operates in environments up to 175 deg F
  • Significantly lower cost, compared to explosion proof Freon air conditioners
  • Reduce operating cost with mechanical thermostat turning the unit on only when necessary
  • Very quiet, 62 dBA operation, 78% quieter than typical vortex coolers
  • Multiple cooling capacities available, to optimize performance and operating cost
  • Little maintenance required, as compared to Freon A/C and fans
  • Use no refrigerants
  • Sleek, modern design

FEATURES

  • ATEX Certified Ex II 2 GD T3
  • UL Classified Class I Div. 1, Class II Div. 1 and Class III
  • Ex h llC T3 Gb
  • Ex h lllC T200C Db
  • Ta +10 to 80C
  • Tamb 10°C to 80°C (50°F to 175°F)
  • 3 year warranty
  • Small footprint to fit on all enclosures and in confined areas
  • Top, side or front (door) mount models available
  • Maintain temperature between 75 - 100 deg F
  • Supplied with air filter and ducting kit
  • Maintains slight pressurization in the enclosure

SPECIFICATIONS

Rating Thermostat System  Cooling Capacity BTU/hr Air Consumption Scfm Sound Level Item # Specs
ProtEX* Mechanical System 900 15 60 dBA 8115 다운로드
1500 25 66 dBA 8125 다운로드
2500 35 72 dBA 8135 다운로드
5000 70 75 dBA 8170 다운로드

* ATEX Certified Zones 1 & 21

*UL Classified for Class I, Division 1, Groups A, B, C and D, Class II, Division 1, Groups F and G, Class III